Objective. Students will wire a 24 VAC control circuit from a step-down transformer through a thermostat sub-base to a relay coil, verify correct voltage at each point, and explain the function of the R, C, G, Y, and W thermostat terminals.
Most residential and light-commercial HVAC/R systems use a 24 VAC control circuit to operate thermostats, relay coils, and contactor coils. Running low voltage to a wall thermostat is far safer for occupants than running line voltage, and it allows long wire runs with inexpensive 18 AWG thermostat wire. The control transformer is the device that converts 120 VAC (or 240 VAC) line power down to 24 VAC for the control circuit.
A control transformer is a step-down transformer with two windings wound around a common iron core:
Transformers work on electromagnetic induction. Alternating current in the primary creates a changing magnetic field that induces a voltage in the secondary. The ratio of primary turns to secondary turns determines the voltage ratio.
VA Rating – Transformers are rated in volt-amperes (VA), not watts, because control loads are often inductive (coils). A typical residential system uses a 40 VA transformer. To select the correct VA rating, add up the VA draw of every load the secondary must power simultaneously (thermostat electronics, relay coils, contactor coils, damper actuators, etc.) and choose a transformer whose rating equals or exceeds that total. Using an undersized transformer causes the secondary voltage to sag under load, leading to chatter or failure to pull in contactors.
Sizing formula:
> VA required = Σ (volts × amperes) of all simultaneous secondary loads
Because the output is 24 VAC, you can also write: VA = 24 V × total secondary amperes.
The low-voltage thermostat sub-base is the control hub of the circuit. Each terminal letter has a standard meaning recognized across the industry:
| Terminal | Function |
|----------|----------|
| R | 24 VAC hot (from transformer secondary) |
| C | Common – the return path to the transformer secondary |
| G | Fan relay (indoor blower – fan only) |
| Y | Compressor contactor (cooling) |
| W | Heat relay or gas valve (heating) |
Some sub-bases split R into Rh (heat) and Rc (cool) with a factory jumper that can be removed when a system has two separate transformers.
The R and C terminals form the two legs of the 24 VAC circuit. When the thermostat closes a switch between R and Y, for example, current flows from R through the switch to Y, through the contactor coil, and back to C – completing the circuit and energizing the coil.
Follow the circuit from source to load:
1. Transformer primary – 120 VAC supply → primary winding.
2. Transformer secondary – 24 VAC output → one lead to terminal R, other lead to terminal C.
3. Thermostat switch (Y terminal closed) → 24 VAC passes through Y to the contactor coil.
4. Other side of contactor coil → returns to C.
5. Coil energized → contactor pulls in → compressor starts.
The G and W terminals work identically; the thermostat simply closes a different internal switch to route 24 VAC through G to the fan relay coil, or through W to the heat relay or gas valve.
Personal Protective Equipment (PPE): Safety glasses are required whenever working with live circuits. Although 24 VAC is low voltage, the 120 VAC primary side carries lethal potential.
Lockout/Tagout (LOTO): Before making or changing any wiring connection, de-energize the training board and apply your personal lockout device per your shop's LOTO procedure. Never work on a live primary side.
Inspect before energizing: Have the instructor visually check all wiring before applying power. A miswired transformer primary can damage equipment or create a shock hazard.
Multimeter range selection: Set the meter to an AC voltage range higher than the expected reading before probing. Confirm meter leads are in the correct jacks (V and COM) before touching probes to terminals.
No unapproved substitutions: Use only the 40 VA, 120/24 VAC transformer specified for this lab. Substituting a higher primary-voltage transformer on a 120 VAC supply can destroy the secondary winding.
When a circuit does not operate, half-splitting finds the fault efficiently:
1. Identify the two ends of the suspect circuit.
2. Measure voltage at the midpoint. If voltage is present past the midpoint, the fault is in the second half; if absent, the fault is in the first half.
3. Repeat, halving the remaining suspect section each time.
4. This method finds the fault in the fewest possible measurements.
Document each measurement in your lab log: the point tested, the reading, and your conclusion. This written record is the professional standard for diagnostic work.
Answer each question, then check it. Nothing is recorded; this is your own practice.
A free tech program — complimentary, as our commitment to get America working. Help us build VoTechWorks. Tell us what works, what doesn’t, and what you want to learn.
Does the school offer financial aid?
No. We don’t offer financial aid because we’re free. No, really: completely free.
Do you offer industry certification?
No. We are not certified yet, so we can’t offer that to students. What we do offer is knowledge and understanding of a trade.
Enroll first in the trade you’re interested in. You get your key, your program opens, and you begin studying.
Enroll free →