Objective. Students will safely discharge, test, and evaluate run capacitors and start capacitors using a capacitance meter, and replace an out-of-tolerance capacitor while following discharge and LOTO procedures.
Capacitors store an electrical charge and release it to create a phase shift in the current supplied to single-phase motors. Without that phase shift, a single-phase AC motor cannot develop enough starting torque or run efficiently. HVAC/R equipment relies on two types of capacitors for motor operation: run capacitors and start capacitors. Many condensers also use a dual-round capacitor, which combines both functions in one cylindrical can.
A run capacitor stays in the circuit the entire time the motor operates. It is an oil-filled, metal-can component rated in microfarads (µF) and voltage — typically in the range of 3 µF to 70 µF for HVAC motors. Because it runs continuously, it must be a high-quality, low-loss type. Run capacitors are usually rated at 370 VAC or 440 VAC. A run capacitor that drifts out of tolerance forces the motor winding to work harder, raises amperage draw, and shortens motor life.
A start capacitor is switched into the circuit only during the brief start-up period — usually by a start relay or potential relay — and then removed once the motor reaches approximately 75–80 percent of running speed. Start capacitors are electrolytic, rated in much higher µF values (often 88 µF to several hundred µF), and are not designed for continuous-duty use. They are identifiable by their plastic or Bakelite case and the bleed resistor wired across their terminals, which slowly dissipates charge when the capacitor is switched out.
A dual-round (also called a dual-run) capacitor replaces two separate run capacitors with a single cylindrical component. One section serves the compressor motor; the other serves the condenser fan motor. Terminals are labeled C (common), HERM (hermetic compressor), and FAN. When replacing a dual-round capacitor, both µF ratings — printed separately on the label — must match the equipment specifications.
A capacitor can hold a lethal charge even after the unit has been de-energized. Never touch capacitor terminals with bare hands or uninsulated tools before discharging. The discharge must be performed before any hands-on work, every single time.
Two-resistor discharge procedure:
1. Apply LOTO — lock out, tag out the disconnect, and verify zero voltage at the unit with a DMM.
2. Obtain the 10,000 Ω, 5 W discharge resistor tool with insulated leads.
3. With insulated-grip tools, touch one lead to one terminal and the other lead to the second terminal simultaneously. Hold contact for at least five seconds.
4. For a dual-round capacitor, discharge HERM-to-C, FAN-to-C, and then HERM-to-FAN.
5. Verify with a DMM set to DC volts that terminal voltage reads zero before proceeding.
Using a screwdriver blade to short capacitor terminals is prohibited — the arc can damage the capacitor, destroy the tool, and injure you. Use only the resistor discharge tool.
Set the meter to capacitance (µF) mode. After discharging, touch the meter probes to the capacitor terminals. For a dual-round, measure each section separately (HERM-to-C, then FAN-to-C). Record the measured value and compare it to the nameplate-rated µF.
Industry-accepted tolerance for run capacitors: ±6% of nameplate rating. Some manufacturers publish ±5%; use the tolerance stated on the equipment documentation when available. A capacitor reading outside that range is considered failed and must be replaced.
Start capacitors have a wider rated tolerance range printed on the component itself (for example, 88–108 µF). The measured value must fall within the printed range.
1. With LOTO applied and capacitor discharged, photograph the existing wiring or sketch the wiring diagram before removing any wires.
2. Remove wires one at a time, labeling each with tape if needed.
3. Release the mounting strap or bracket and remove the old capacitor.
4. Install the new capacitor — same µF ratings for each section and equal or greater voltage rating.
5. Reconnect wires: C (common) to the common wire, HERM to the compressor start/run wire, FAN to the fan motor wire. Verify against the unit wiring diagram before re-energizing.
6. Remove LOTO per procedure, energize the unit, and monitor starting amperage and running amperage to confirm normal operation.
Record the nameplate µF rating, measured µF value, percent deviation, pass/fail determination, and action taken on the service report form. Good documentation protects you legally and helps the next technician.
Safety glasses are required at all times. Insulated-grip tools (1,000 V rated) must be used whenever handling capacitors. Do not handle capacitors with wet hands. If a capacitor is visibly bulged, leaking oil, or has a ruptured bleed vent, treat it as hazardous and inform the instructor before touching it.
Answer each question, then check it. Nothing is recorded; this is your own practice.
A free tech program — complimentary, as our commitment to get America working. Help us build VoTechWorks. Tell us what works, what doesn’t, and what you want to learn.
Does the school offer financial aid?
No. We don’t offer financial aid because we’re free. No, really: completely free.
Do you offer industry certification?
No. We are not certified yet, so we can’t offer that to students. What we do offer is knowledge and understanding of a trade.
Enroll first in the trade you’re interested in. You get your key, your program opens, and you begin studying.
Enroll free →